AWG to mm² Wire Gauge Converter

Convert between American Wire Gauge (AWG) and metric cross‑sectional area (mm²) instantly.

AWG to mm² Converter


Area & Diameter are fixed by AWG spec. Only Resistance changes with material.

mm² to AWG Converter


Please enter a valid positive number.
mm² to AWG matching depends only on cross‑sectional area, not material.

AWG Reference Table (Copper Conductor)


AWG Area (mm²) Diameter (mm) Copper Resistance (Ω/km)
4/0107.2211.6840.1608
3/084.9710.4040.2028
2/067.409.2660.2557
1/053.498.2510.3224
042.417.3480.4066
133.626.5440.5129
226.675.8270.6465
321.155.1890.8152
416.774.6211.028
513.304.1151.296
610.553.6651.634
78.3873.2642.061
86.6312.9062.598
95.2612.5883.277
105.262.5883.28
123.312.0535.21
142.081.6288.28
161.311.29113.2
180.8231.02420.9
200.5190.81233.2
220.3260.64452.8
240.2050.51184.2
260.1290.405133.9
280.08100.321212.9
300.05090.255338.6

AWG vs. mm²: What's the Difference?


  • AWG (American Wire Gauge) is a standardized wire size measurement system used primarily in the United States. The higher the AWG number, the smaller the wire diameter.
  • mm² represents the cross‑sectional area of the conductor in square millimeters and is the standard metric measurement used worldwide.
  • In AWG, a smaller number means a thicker wire; in mm², a larger number means a thicker wire.
  • AWG and mm² are not a simple integer correspondence — they follow different measurement systems, so conversion requires referencing standardized tables.
  • Cable selection also requires consideration of ampacity, voltage drop, temperature rating, and installation conditions — not just wire gauge alone.

Frequently Asked Questions


AWG (American Wire Gauge) is a U.S. standard for measuring wire diameter, where a smaller number indicates a thicker conductor. mm² measures the cross‑sectional area of the conductor in metric units. They use different measurement systems, so conversion between them is not a simple ratio — you need to reference standardized conversion tables. Both describe the same physical conductor but through different numerical systems.

AWG to mm² conversion is done by looking up the standard wire gauge table. Each AWG size corresponds to a specific cross‑sectional area in mm². For example, 16 AWG equals 1.31 mm², 12 AWG equals 3.31 mm², and 10 AWG equals 5.26 mm². You can use the converter above for instant results, or refer to the AWG reference table on this page.

16 AWG has a cross‑sectional area of 1.31 mm² and a conductor diameter of 1.291 mm. For copper conductors, the resistance is 13.2 Ω/km. This is one of the most commonly used wire sizes in electronic wiring harnesses and low‑voltage control circuits.

18 AWG has a cross‑sectional area of 0.823 mm² and a conductor diameter of 1.024 mm. For copper conductors, the resistance is 20.9 Ω/km. 18 AWG is widely used in automotive wiring harnesses, LED lighting, and general‑purpose low‑current applications.

A larger AWG number means a thinner wire. For example, 24 AWG is much thinner than 10 AWG. This is the opposite of mm², where a larger number means a thicker conductor. When converting from AWG to mm², remember: higher AWG number = smaller mm² area = thinner wire.